CVE-2019-13927
published 2019-12-12CVE-2019-13927: A vulnerability has been identified in Desigo PX automation controllers PXC00-E.D, PXC50-E.D, PXC100-E.D, PXC200-E.D with Desigo PX Web modules PXA40-W0…
PriorityP336medium5.3CVSS 3.1
AVNACLPRNUINSUCNINAL
EXPLOIT
EPSS
1.68%
74.0th percentile
A vulnerability has been identified in Desigo PX automation controllers PXC00-E.D, PXC50-E.D, PXC100-E.D, PXC200-E.D with Desigo PX Web modules PXA40-W0, PXA40-W1, PXA40-W2 (All firmware versions < V6.00.320), Desigo PX automation controllers PXC00-U, PXC64-U, PXC128-U with Desigo PX Web modules PXA30-W0, PXA30-W1, PXA30-W2 (All firmware versions < V6.00.320), Desigo PX automation controllers PXC22.1-E.D, PXC36-E.D, PXC36.1-E.D with activated web server (All firmware versions < V6.00.320). The device contains a vulnerability that could allow an attacker to cause a denial of service condition on the device's web server by sending a specially crafted HTTP message to the web server port (tcp/80). The security vulnerability could be exploited by an attacker with network access to an affected device. Successful exploitation requires no system privileges and no user interaction. An attacker could use the vulnerability to compromise the availability of the device's web service. While the device itself stays operational, the web server responds with HTTP status code 404 (Not found) to any further request. A reboot is required to recover the web interface. At the time of advisory publication no public exploitation of this security vulnerability was known.
Affected
16 ranges
| Vendor | Product | Version range | Fixed in |
|---|---|---|---|
| siemens | pxa30-w0_firmware | < 6.00.320 | 6.00.320 |
| siemens | pxa30-w1_firmware | < 6.00.320 | 6.00.320 |
| siemens | pxa30-w2_firmware | < 6.00.320 | 6.00.320 |
| siemens | pxa40-w0_firmware | < 6.00.320 | 6.00.320 |
| siemens | pxa40-w1_firmware | < 6.00.320 | 6.00.320 |
| siemens | pxa40-w2_firmware | < 6.00.320 | 6.00.320 |
| siemens | pxc00-e.d_firmware | < 6.00.320 | 6.00.320 |
| siemens | pxc00-u_firmware | < 6.00.320 | 6.00.320 |
| siemens | pxc100-e.d_firmware | < 6.00.320 | 6.00.320 |
| siemens | pxc128-u_firmware | < 6.00.320 | 6.00.320 |
| siemens | pxc200-e.d_firmware | < 6.00.320 | 6.00.320 |
| siemens | pxc22.1-e.d_firmware | < 6.00.320 | 6.00.320 |
| siemens | pxc36-e.d_firmware | < 6.00.320 | 6.00.320 |
| siemens | pxc36.1-e.d_firmware | < 6.00.320 | 6.00.320 |
| siemens | pxc50-e.d_firmware | < 6.00.320 | 6.00.320 |
| siemens | pxc64-u_firmware | < 6.00.320 | 6.00.320 |
CVSS provenance
nvdv3.15.3MEDIUMCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L
nvdv2.05.0MEDIUMAV:N/AC:L/Au:N/C:N/I:N/A:P
CVEs like this are exactly what “Exploited This Week” covers.
Every Monday: what got weaponized or added to CISA KEV in the last seven days — each CVE cross-linked to its PoC, Nuclei template, and detection rule. Free, one email a week, unsubscribe in one click.
GHSA
GHSA-3phq-67rm-2hq8: A vulnerability has been identified in Desigo PX automation controllers PXC00-E
ghsa_unreviewed·2022-05-24
CVE-2019-13927 [MEDIUM] GHSA-3phq-67rm-2hq8: A vulnerability has been identified in Desigo PX automation controllers PXC00-E
A vulnerability has been identified in Desigo PX automation controllers PXC00-E.D, PXC50-E.D, PXC100-E.D, PXC200-E.D with Desigo PX Web modules PXA40-W0, PXA40-W1, PXA40-W2 (All firmware versions < V6.00.320), Desigo PX automation controllers PXC00-U, PXC64-U, PXC128-U with Desigo PX Web modules PXA30-W0, PXA30-W1, PXA30-W2 (All firmware versions < V6.00.320), Desigo PX automation controllers PXC22.1-E.D, PXC36-E.D, PXC36.1-E.D with activated web server (All firmware versions < V6.00.320). The device contains a vulnerability that could allow an attacker to cause a denial of service condition on the device's web server by sending a specially crafted HTTP message to the web server port (tcp/80). The security vulnerability could be exploited by an attacker with network access to an affected d
CISA ICS
Siemens Desigo PX Devices
cisa_ics·2019-11-14·CVSS 5.3
[MEDIUM] Siemens Desigo PX Devices
## Archived Content In an effort to keep CISA.gov current, the archive contains outdated information that may not reflect current policy or programs.
ICS Advisory
##
Siemens Desigo PX Devices
Last RevisedNovember 14, 2019
Alert CodeICSA-19-318-03
## 1. EXECUTIVE SUMMARY
- CVSS v3 5.3
- ATTENTION: Exploitable remotely/low skill level to exploit
- Vendor: Siemens
- Equipment: Desigo PX Devices
- Vulnerability: External Control of Assumed-Immutable Web Parameter
## 2. RISK EVALUATION
Successful exploitation of this vulnerability could allow an attacker to cause a denial-of-service condition on the device’s web server, requiring a reboot to recover the web interface.
## 3. TECHNICAL DETAILS
## 3.1 AFFECTED PRODUCTS
The following Desigo
No detection rules found.
No writeups or analysis indexed.
2019-12-12
Published