CVE-2019-14930
published 2019-10-28CVE-2019-14930: An issue was discovered on Mitsubishi Electric Europe B.V. ME-RTU devices through 2.02 and INEA ME-RTU devices through 3.0. Undocumented hard-coded user…
PriorityP260critical9.8CVSS 3.1
AVNACLPRNUINSUCHIHAH
EPSS
2.34%
81.5th percentile
An issue was discovered on Mitsubishi Electric Europe B.V. ME-RTU devices through 2.02 and INEA ME-RTU devices through 3.0. Undocumented hard-coded user passwords for root, ineaadmin, mitsadmin, and maint could allow an attacker to gain unauthorised access to the RTU. (Also, the accounts ineaadmin and mitsadmin are able to escalate privileges to root without supplying a password due to insecure entries in /etc/sudoers on the RTU.)
Affected
2 ranges
| Vendor | Product | Version range | Fixed in |
|---|---|---|---|
| inea | me-rtu_firmware | <= 3.0 | — |
| mitsubishielectric | smartrtu_firmware | <= 2.02 | — |
CVSS provenance
nvdv3.19.8CRITICALCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
nvdv2.010.0CRITICALAV:N/AC:L/Au:N/C:C/I:C/A:C
Stop checking back — get the weekly exploitation signal.
Every Monday: what got weaponized or added to CISA KEV in the last seven days — each CVE cross-linked to its PoC, Nuclei template, and detection rule. Free, one email a week, unsubscribe in one click.
CISA ICS
Mitsubishi Electric Europe B.V. smartRTU and INEA ME-RTU
cisa_ics·2019-09-10·CVSS 7.5
[HIGH] Mitsubishi Electric Europe B.V. smartRTU and INEA ME-RTU
## Archived Content In an effort to keep CISA.gov current, the archive contains outdated information that may not reflect current policy or programs.
ICS Advisory
##
Mitsubishi Electric Europe B.V. smartRTU and INEA ME-RTU
Last RevisedSeptember 09, 2021
Alert CodeICSA-21-252-03
## 1. EXECUTIVE SUMMARY
- CVSS v3 9.8
- ATTENTION: Exploitable remotely/low attack complexity
- Vendor: Mitsubishi Electric Europe B.V.
- Equipment: smartRTU and INEA ME-RTU
- Vulnerabilities: OS Command Injection, Improper Access Control, Cross-site Scripting, Use of Hard-coded Credentials, Unprotected Storage of Credentials, Incorrect Default Permissions
## 2. REPOSTED INFORMATION
This advisory is a follow-up to a CISA product update titled ICS-ALERT-19-225-01
GHSA
GHSA-xwpv-xmw2-88gc: An issue was discovered on Mitsubishi Electric ME-RTU devices through 2
ghsa_unreviewed·2022-05-24
CVE-2019-14930 [CRITICAL] CWE-798 GHSA-xwpv-xmw2-88gc: An issue was discovered on Mitsubishi Electric ME-RTU devices through 2
An issue was discovered on Mitsubishi Electric ME-RTU devices through 2.02 and INEA ME-RTU devices through 3.0. Undocumented hard-coded user passwords for root, ineaadmin, mitsadmin, and maint could allow an attacker to gain unauthorised access to the RTU. (Also, the accounts ineaadmin and mitsadmin are able to escalate privileges to root without supplying a password due to insecure entries in /etc/sudoers on the RTU.)
No detection rules found.
No public exploits indexed.
No writeups or analysis indexed.
2019-10-28
Published