CVE-2019-5620
published 2020-04-29CVE-2019-5620: ABB MicroSCADA Pro SYS600 version 9.3 suffers from an instance of CWE-306: Missing Authentication for Critical Function.
PriorityP181critical9.8CVSS 3.1
AVNACLPRNUINSUCHIHAH
EXPLOIT
EPSS
70.08%
99.3th percentile
ABB MicroSCADA Pro SYS600 version 9.3 suffers from an instance of CWE-306: Missing Authentication for Critical Function.
Affected
2 ranges
| Vendor | Product | Version range | Fixed in |
|---|---|---|---|
| abb | microscada_pro_sys600 | — | — |
| hitachienergy | microscada_pro_sys600 | — | — |
Detection & IOCsextracted from sources · hover to see the quote
- →Monitor for unauthenticated EXECUTE operation requests targeting the wserver.exe component on ABB MicroSCADA SYS600 9.3 systems. ↗
- →Alert on presence or execution of wserver.exe in ABB MicroSCADA environments; the component is disabled by default but enabled when a project uses the SCIL function WORKSTATION_CALL. ↗
- →Exploit targets Windows XP SP3 and Windows 7 SP1 hosts running ABB MicroSCADA Pro SYS600 9.3; scope network monitoring to these OS/version combinations in OT environments. ↗
- ·The vulnerable wserver.exe component is disabled by default; exploitation is only possible when a project has explicitly enabled it via the SCIL WORKSTATION_CALL function, limiting the exposed attack surface. ↗
- ·The vulnerability is classified as CWE-306 (Missing Authentication for Critical Function), meaning no credentials are required to trigger remote code execution via EXECUTE operations. ↗
CVSS provenance
nvdv3.19.8CRITICALCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
nvdv2.07.5HIGHAV:N/AC:L/Au:N/C:P/I:P/A:P
CVEs like this are exactly what “Exploited This Week” covers.
Every Monday: what got weaponized or added to CISA KEV in the last seven days — each CVE cross-linked to its PoC, Nuclei template, and detection rule. Free, one email a week, unsubscribe in one click.
No detection rules found.
No writeups or analysis indexed.
2020-04-29
Published