CVE-2019-6553
published 2019-04-04CVE-2019-6553: A vulnerability was found in Rockwell Automation RSLinx Classic versions 4.10.00 and prior. An input validation issue in a .dll file of RSLinx Classic where…
PriorityP270critical9.8CVSS 3.1
AVNACLPRNUINSUCHIHAH
EPSS
50.03%
98.8th percentile
A vulnerability was found in Rockwell Automation RSLinx Classic versions 4.10.00 and prior. An input validation issue in a .dll file of RSLinx Classic where the data in a Forward Open service request is passed to a fixed size buffer, allowing an attacker to exploit a stack-based buffer overflow condition.
Affected
2 ranges
| Vendor | Product | Version range | Fixed in |
|---|---|---|---|
| rockwell_automation | rslinx_classic | — | — |
| rockwellautomation | rslinx | <= 4.10.00 | — |
Detection & IOCsextracted from sources · hover to see the quote
- →Monitor for malformed Forward Open service requests sent to UDP port 44818, which is the attack vector for the stack-based buffer overflow in RSLinx Classic's .dll file. ↗
- ·No known public exploits specifically target this vulnerability at time of advisory publication. ↗
CVSS provenance
nvdv3.19.8CRITICALCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
nvdv2.07.5HIGHAV:N/AC:L/Au:N/C:P/I:P/A:P
Stop checking back — get the weekly exploitation signal.
Every Monday: what got weaponized or added to CISA KEV in the last seven days — each CVE cross-linked to its PoC, Nuclei template, and detection rule. Free, one email a week, unsubscribe in one click.
GHSA
GHSA-2q9x-jr84-x65p: A vulnerability was found in Rockwell Automation RSLinx Classic versions 4
ghsa_unreviewed·2022-05-13
CVE-2019-6553 [CRITICAL] CWE-787 GHSA-2q9x-jr84-x65p: A vulnerability was found in Rockwell Automation RSLinx Classic versions 4
A vulnerability was found in Rockwell Automation RSLinx Classic versions 4.10.00 and prior. An input validation issue in a .dll file of RSLinx Classic where the data in a Forward Open service request is passed to a fixed size buffer, allowing an attacker to exploit a stack-based buffer overflow condition.
CISA ICS
Rockwell Automation RSLinx Classic
cisa_ics·2019-03-05·CVSS 9.8
[CRITICAL] Rockwell Automation RSLinx Classic
## Archived Content In an effort to keep CISA.gov current, the archive contains outdated information that may not reflect current policy or programs.
ICS Advisory
##
Rockwell Automation RSLinx Classic
Last RevisedMarch 05, 2019
Alert CodeICSA-19-064-01
## 1. EXECUTIVE SUMMARY
-
CVSS v3 10.0
- ATTENTION: Exploitable remotely/low skill level to exploit
- Vendor: Rockwell Automation
- Equipment: RSLinx Classic
- Vulnerability: Stack-based Buffer Overflow
## 2. RISK EVALUATION
Successful exploitation of this vulnerability could allow a remote attacker to execute arbitrary code on the target device.
## 3. TECHNICAL DETAILS
## 3.1 AFFECTED PRODUCTS
The following versions of RSLinx Classic, PLC communications software, are affected:
- RSL