CVE-2020-10920
published 2020-07-23CVE-2020-10920: This vulnerability allows remote attackers to execute arbitrary code on affected installations of C-MORE HMI EA9 Firmware version 6.52 touch screen panels…
PriorityP272critical9.8CVSS 3.1
AVNACLPRNUINSUCHIHAH
EPSS
4.92%
91.0th percentile
This vulnerability allows remote attackers to execute arbitrary code on affected installations of C-MORE HMI EA9 Firmware version 6.52 touch screen panels. Authentication is not required to exploit this vulnerability. The specific flaw exists within the control service, which listens on TCP port 9999 by default. The issue results from the lack of authentication prior to allowing alterations to the system configuration. An attacker can leverage this vulnerability to execute code in the context of the device. Was ZDI-CAN-10493.
Affected
2 ranges
| Vendor | Product | Version range | Fixed in |
|---|---|---|---|
| automationdirect | c-more_hmi_ea9_firmware | — | — |
| c-more | hmi_ea9 | — | — |
CVSS provenance
nvdv3.19.8CRITICALCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
nvdv3.09.8CRITICALCVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
nvdv2.07.5HIGHAV:N/AC:L/Au:N/C:P/I:P/A:P
Stop checking back — get the weekly exploitation signal.
Every Monday: what got weaponized or added to CISA KEV in the last seven days — each CVE cross-linked to its PoC, Nuclei template, and detection rule. Free, one email a week, unsubscribe in one click.
No detection rules found.
No public exploits indexed.
No writeups or analysis indexed.
2020-07-23
Published