CVE-2020-27251
published 2020-11-26CVE-2020-27251: A heap overflow vulnerability exists within FactoryTalk Linx Version 6.11 and prior. This vulnerability could allow a remote, unauthenticated attacker to send…
PriorityP266critical9.8CVSS 3.1
AVNACLPRNUINSUCHIHAH
EPSS
5.46%
91.7th percentile
A heap overflow vulnerability exists within FactoryTalk Linx Version 6.11 and prior. This vulnerability could allow a remote, unauthenticated attacker to send malicious port ranges, which could result in remote code execution.
Affected
2 ranges
| Vendor | Product | Version range | Fixed in |
|---|---|---|---|
| rockwellautomation | factorytalk_linx | <= 6.11 | — |
| rockwellautomation | factorytalk_linx | — | — |
Detection & IOCsextracted from sources · hover to see the quote
- →Detect malicious port range values sent remotely to FactoryTalk Linx (Version 6.11 and prior) — heap overflow triggered via crafted port ranges in network packets ↗
- →No authentication required for exploitation — monitor for unauthenticated inbound connections to FactoryTalk Linx service ports from unexpected sources ↗
- →No known public exploits exist as of advisory date — prioritize detection of anomalous/malformed packets targeting FactoryTalk Linx rather than signature-based exploit matching ↗
- ·Vulnerability affects FactoryTalk Linx Version 6.11 and prior; patched versions are 6.10/6.11 with Patch Answer ID 1126433 or upgrade to v6.20 — ensure detection rules are scoped to unpatched instances ↗
CVSS provenance
nvdv3.19.8CRITICALCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
nvdv2.07.5HIGHAV:N/AC:L/Au:N/C:P/I:P/A:P
Stop checking back — get the weekly exploitation signal.
Every Monday: what got weaponized or added to CISA KEV in the last seven days — each CVE cross-linked to its PoC, Nuclei template, and detection rule. Free, one email a week, unsubscribe in one click.
CISA ICS
Rockwell Automation FactoryTalk Linx
cisa_ics·2020-11-24·CVSS 9.8
[CRITICAL] Rockwell Automation FactoryTalk Linx
## Archived Content In an effort to keep CISA.gov current, the archive contains outdated information that may not reflect current policy or programs.
ICS Advisory
##
Rockwell Automation FactoryTalk Linx
Last RevisedNovember 24, 2020
Alert CodeICSA-20-329-01
## 1. EXECUTIVE SUMMARY
- CVSS v3 9.8
- ATTENTION: Exploitable remotely/Low skill level to exploit
- Vendor: Rockwell Automation
- Equipment: FactoryTalk Linx
- Vulnerabilities: Improper Input Validation, Heap-based Buffer Overflow
## 2. RISK EVALUATION
Successful exploitation of these vulnerabilities could allow a denial-of-service condition, remote code execution, or leak information that could be used to bypass address space layout randomization (ASLR).
## 3. TECHNICAL DETAILS
GHSA
GHSA-7hx6-pmgh-3p98: A heap overflow vulnerability exists within FactoryTalk Linx Version 6
ghsa_unreviewed·2022-05-24
CVE-2020-27251 [CRITICAL] CWE-122 GHSA-7hx6-pmgh-3p98: A heap overflow vulnerability exists within FactoryTalk Linx Version 6
A heap overflow vulnerability exists within FactoryTalk Linx Version 6.11 and prior. This vulnerability could allow a remote, unauthenticated attacker to send malicious port ranges, which could result in remote code execution.
No detection rules found.
No public exploits indexed.
No writeups or analysis indexed.
2020-11-26
Published