cbcvebase.
CVE-2021-22743
published 2021-05-26

CVE-2021-22743: Improper Check for Unusual or Exceptional Conditions vulnerability exists in Triconex TCM 4351B installed on Tricon V11.3.x systems that could cause module…

low3.9CVSS 3.1
AVPACLPRHUINSUCNINAH
Improper Check for Unusual or Exceptional Conditions vulnerability exists in Triconex TCM 4351B installed on Tricon V11.3.x systems that could cause module reset when TCM receives malformed TriStation packets while the write-protect keyswitch is in the program position.

Affected

3 ranges
VendorProductVersion rangeFixed in
schneider-electrictcm_4351b_firmware
schneider-electrictcm_4351b_firmware>= 11.3.0 < 11.5.111.5.1
schneider-electrictriconex_model_3009_mp_firmware>= 11.3.0 < 11.8.011.8.0