CVE-2021-22802
published 2022-02-11CVE-2021-22802: A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could result in remote code execution due to missing length check on user…
PriorityP275critical9.8CVSS 3.1
AVNACLPRNUINSUCHIHAH
EPSS
20.16%
97.1th percentile
A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could result in remote code execution due to missing length check on user supplied data, when a constructed message is received on the network. Affected Product: Interactive Graphical SCADA System Data Collector (dc.exe) (V15.0.0.21243 and prior)
Affected
1 ranges
| Vendor | Product | Version range | Fixed in |
|---|---|---|---|
| schneider-electric | interactive_graphical_scada_system_data_collector | <= 15.0.0.21243 | — |
Detection & IOCsextracted from sources · hover to see the quote
- →Target process is dc.exe (IGSS Data Collector); monitor for network-received constructed messages triggering buffer overflow in dc.exe versions V15.0.0.21243 and prior ↗
- →Monitor for unexpected child processes or code execution spawned from dc.exe, indicating successful exploitation of the buffer overflow ↗
- ·Vulnerability is exploitable remotely with no authentication and low attack complexity (CVSS 9.8); affected versions are IGSS Data Collector dc.exe V15.0.0.21243 and prior — fixed in V15.0.0.21244 ↗
- ·No known public exploits specifically targeting this vulnerability at time of advisory publication ↗
CVSS provenance
nvdv3.19.8CRITICALCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
nvdv2.07.5HIGHAV:N/AC:L/Au:N/C:P/I:P/A:P
Stop checking back — get the weekly exploitation signal.
Every Monday: what got weaponized or added to CISA KEV in the last seven days — each CVE cross-linked to its PoC, Nuclei template, and detection rule. Free, one email a week, unsubscribe in one click.
CISA ICS
Schneider Electric IGSS
cisa_ics·2021-10-12·CVSS 9.8
[CRITICAL] Schneider Electric IGSS
## Archived Content In an effort to keep CISA.gov current, the archive contains outdated information that may not reflect current policy or programs.
ICS Advisory
##
Schneider Electric IGSS
Last RevisedOctober 12, 2021
Alert CodeICSA-21-285-03
## 1. EXECUTIVE SUMMARY
- CVSS v3 9.8
- ATTENTION: Exploitable remotely/low attack complexity
- Vendor: Schneider Electric
- Equipment: IGSS (Interactive Graphical SCADA System)
- Vulnerabilities: Classic Buffer Overflow, Unrestricted Upload of File with Dangerous Type, Path Traversal, Missing Authentication for Critical Function
## 2. RISK EVALUATION
Successful exploitation of these vulnerabilities could allow an attacker to gain code execution, read/delete files, and create arbitrary files.
##
GHSA
GHSA-frmp-r2qj-7qjr: A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could result in remote code execution due to missing length check on u
ghsa_unreviewed·2022-02-12
CVE-2021-22802 [CRITICAL] CWE-120 GHSA-frmp-r2qj-7qjr: A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could result in remote code execution due to missing length check on u
A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could result in remote code execution due to missing length check on user supplied data, when a constructed message is received on the network. Affected Product: Interactive Graphical SCADA System Data Collector (dc.exe) (V15.0.0.21243 and prior)