CVE-2022-40202
published 2022-10-31CVE-2022-40202: The database backup function in Delta Electronics InfraSuite Device Master Versions 00.00.01a and prior lacks proper authentication. An attacker could provide…
PriorityP265critical9.8CVSS 3.1
AVNACLPRNUINSUCHIHAH
EPSS
1.24%
65.5th percentile
The database backup function in Delta Electronics InfraSuite Device Master Versions 00.00.01a and prior lacks proper authentication. An attacker could provide malicious serialized objects which, when deserialized, could activate an opcode for a backup scheduling function without authentication. This function allows the user to designate all function arguments and the file to be executed. This could allow the attacker to start any new process and achieve remote code execution.
Affected
2 ranges
| Vendor | Product | Version range | Fixed in |
|---|---|---|---|
| delta_electronics | infrasuite_device_master | <= 00.00.01a | — |
| deltaww | infrasuite_device_master | < 00.00.02a | 00.00.02a |
Stop checking back — get the weekly exploitation signal.
Every Monday: what got weaponized or added to CISA KEV in the last seven days — each CVE cross-linked to its PoC, Nuclei template, and detection rule. Free, one email a week, unsubscribe in one click.
GHSA
GHSA-qmpg-9h7f-2x2x: The database backup function in Delta Electronics InfraSuite Device Master Versions 00
ghsa_unreviewed·2022-11-01
CVE-2022-40202 [CRITICAL] CWE-306 GHSA-qmpg-9h7f-2x2x: The database backup function in Delta Electronics InfraSuite Device Master Versions 00
The database backup function in Delta Electronics InfraSuite Device Master Versions 00.00.01a and prior lacks proper authentication. An attacker could provide malicious serialized objects which, when deserialized, could activate an opcode for a backup scheduling function without authentication. This function allows the user to designate all function arguments and the file to be executed. This could allow the attacker to start any new process and achieve remote code execution.
CISA ICS
Delta Electronics InfraSuite Device Master (Update A)
cisa_ics·2022-10-25·CVSS 9.8
[CRITICAL] Delta Electronics InfraSuite Device Master (Update A)
ICS Advisory
##
Delta Electronics InfraSuite Device Master (Update A)
Last RevisedJanuary 18, 2023
Alert CodeICSA-22-298-07
## 1. EXECUTIVE SUMMARY
- CVSS v3 9.8
- ATTENTION: Exploitable remotely/low attack complexity
- Vendor: Delta Electronics
- Equipment: InfraSuite Device Master
- Vulnerabilities: Deserialization of Untrusted Data, Path Traversal, Missing Authentication for Critical Function
## 2. UPDATE OR REPOSTED INFORMATION
This updated advisory is a follow-up to the original advisory titled ICSA-22-298-07 Delta Electronics InfraSuite Device Master that was published October 25, 2022, on the ICS webpage on cisa.gov/ICS.
## 3. RISK EVALUATION
Successful exploitation of these vulnerabilities could allow an unauthenticated attacker to remotely execut
No detection rules found.
No public exploits indexed.
No writeups or analysis indexed.
2022-10-31
Published