CVE-2022-43545
published 2022-11-08CVE-2022-43545: A vulnerability has been identified in POWER METER SICAM Q100 (All versions < V2.50), POWER METER SICAM Q100 (All versions < V2.50), POWER METER SICAM Q100…
PriorityP355high8.8CVSS 3.1
AVNACLPRLUINSUCHIHAH
EPSS
1.35%
68.6th percentile
A vulnerability has been identified in POWER METER SICAM Q100 (All versions < V2.50), POWER METER SICAM Q100 (All versions < V2.50), POWER METER SICAM Q100 (All versions < V2.50), POWER METER SICAM Q100 (All versions < V2.50), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10). Affected devices do not properly validate the RecordType-parameter in requests to the web interface on port 443/tcp. This could allow an authenticated remote attacker to crash the device (followed by an automatic reboot) or to execute arbitrary code on the device.
Affected
5 ranges
| Vendor | Product | Version range | Fixed in |
|---|---|---|---|
| siemens | 7kg9501-0aa01-2aa1_firmware | < 2.50 | 2.50 |
| siemens | 7kg9501-0aa31-2aa1_firmware | < 2.50 | 2.50 |
| siemens | power_meter_sicam_q100 | — | — |
| siemens | sicam_p850 | — | — |
| siemens | sicam_p855 | — | — |
Stop checking back — get the weekly exploitation signal.
Every Monday: what got weaponized or added to CISA KEV in the last seven days — each CVE cross-linked to its PoC, Nuclei template, and detection rule. Free, one email a week, unsubscribe in one click.
CISA ICS
Siemens SICAM Q200 Devices
cisa_ics·2023-06-15·CVSS 7.5
[HIGH] Siemens SICAM Q200 Devices
ICS Advisory
##
Siemens SICAM Q200 Devices
Release DateJune 15, 2023
Alert CodeICSA-23-166-03
## As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global).
## 1. EXECUTIVE SUMMARY
- CVSS v3 9.9
- ATTENTION: Exploitable remotely / low attack complexity
- Vendor: Siemens
- Equipment: POWER METER SICAM Q200 family
- Vulnerabilities: Session Fixation, Improper Input Validation, Cross-Site Request Forgery, Incorrect Permission Assignment for Critical Resource
## 2. RISK EVALUATION
Successful exploitat
CISA ICS
Siemens SICAM Q100
cisa_ics·2022-11-10·CVSS 7.5
[HIGH] Siemens SICAM Q100
## Archived Content In an effort to keep CISA.gov current, the archive contains outdated information that may not reflect current policy or programs.
ICS Advisory
##
Siemens SICAM Q100
Last RevisedNovember 10, 2022
Alert CodeICSA-22-314-11
## 1. EXECUTIVE SUMMARY
- CVSS v3 9.9
- ATTENTION: Exploitable remotely / low attack complexity
- Vendor: Siemens
- Equipment: SICAM Q100
- Vulnerabilities: Session Fixation, Improper Input Validation
## 2. RISK EVALUATION
Successful exploitation of these vulnerabilities could allow an attacker to take over the session of a logged in user or to inject custom code.
## 3. TECHNICAL DETAILS
## 3.1 AFFECTED PRODUCTS
Siemens reports these vulnerabilities affect the following SICAM Q100 products:
- POW
GHSA
GHSA-xvw3-v5p5-pf8m: A vulnerability has been identified in POWER METER SICAM Q100 (All versions < V2
ghsa_unreviewed·2022-11-08
CVE-2022-43545 [HIGH] CWE-20 GHSA-xvw3-v5p5-pf8m: A vulnerability has been identified in POWER METER SICAM Q100 (All versions < V2
A vulnerability has been identified in POWER METER SICAM Q100 (All versions < V2.50), POWER METER SICAM Q100 (All versions < V2.50). Affected devices do not properly validate the RecordType-parameter in requests to the web interface on port 443/tcp. This could allow an authenticated remote attacker to crash the device (followed by an automatic reboot) or to execute arbitrary code on the device.
No detection rules found.
No public exploits indexed.
No writeups or analysis indexed.
https://cert-portal.siemens.com/productcert/pdf/ssa-570294.pdfhttps://cert-portal.siemens.com/productcert/pdf/ssa-572005.pdfhttps://cert-portal.siemens.com/productcert/pdf/ssa-887249.pdfhttps://cert-portal.siemens.com/productcert/pdf/ssa-570294.pdfhttps://cert-portal.siemens.com/productcert/pdf/ssa-572005.pdfhttps://cert-portal.siemens.com/productcert/pdf/ssa-887249.pdf
2022-11-08
Published