CVE-2023-4346
published 2023-08-29

CVE-2023-4346: KNX devices that use KNX Connection Authorization and support Option 1 are, depending on the implementation, vulnerable to being locked and users being unable…

PriorityP180high7.5CVSS 3.1
AVNACLPRNUINSUCNINAH
KEVITW
CISA Known Exploited Vulnerabilitydue 2026-07-29
Exploited in the wild
EPSS
0.85%
54.5th percentile
KNX devices that use KNX Connection Authorization and support Option 1 are, depending on the implementation, vulnerable to being locked and users being unable to reset them to gain access to the device. The BCU key feature on the devices can be used to create a password for the device, but this password can often not be reset without entering the current password. If the device is configured to interface with a network, an attacker with access to that network could interface with the KNX installation, purge all devices without additional security options enabled, and set a BCU key, locking the device. Even if a device is not connected to a network, an attacker with physical access to the device could also exploit this vulnerability in the same way.

Affected

1 ranges
VendorProductVersion rangeFixed in
knx_associationknx_protocol_connection_authorization_option_1

Detection & IOCsextracted from sources · hover to see the quote

  • Attacker with network access can interface with KNX installation, purge all devices without additional security options enabled, and set a BCU key to lock the device
  • Attack is exploitable remotely with low attack complexity and no privileges or user interaction required; monitor KNX network segments for unauthorized BCU key write operations
  • CISA has confirmed active exploitation in the wild; treat any unexpected BCU key changes or device lockouts on KNX installations as a potential incident
  • ·Only KNX devices using Connection Authorization Option 1 where NO BCU Key is currently set are affected; devices with a BCU key already configured are not the primary target of this attack path
  • ·Vulnerability impact depends on implementation; not all KNX Option 1 devices are equally susceptible — behaviour varies by vendor implementation
  • ·Physical access is also a viable attack vector, not just network access; air-gapping alone does not fully mitigate the risk
  • ·Active exploitation has been added to CISA KEV with a remediation due date of 2026-07-29; it is currently not publicly known how the flaw is being abused or by whom

CVSS provenance

nvdv3.17.5HIGHCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
vulncheck7.5HIGH
cisa7.5HIGH