CVE-2024-10456
published 2024-10-30CVE-2024-10456: Delta Electronics InfraSuite Device Master versions prior to 1.0.12 are affected by a deserialization vulnerability that targets the Device-Gateway, which…
PriorityP276critical9.8CVSS 3.1
AVNACLPRNUINSUCHIHAH
EPSS
17.70%
96.8th percentile
Delta Electronics InfraSuite Device Master versions prior to 1.0.12 are affected by a deserialization vulnerability that targets the Device-Gateway, which could allow deserialization of arbitrary .NET objects prior to authentication.
Affected
1 ranges
| Vendor | Product | Version range | Fixed in |
|---|---|---|---|
| delta_electronics | infrasuite_device_master | <= 1.0.12 | — |
Detection & IOCsextracted from sources · hover to see the quote
- →Target component is the Device-Gateway service of Delta Electronics InfraSuite Device Master; monitor for unauthenticated deserialization of arbitrary .NET objects sent to this component ↗
- →Exploitation is possible with no authentication, no user interaction, and low attack complexity over the network — treat any unexpected inbound traffic to the Device-Gateway as high-priority alert ↗
- ·All versions of InfraSuite Device Master up to and including 1.0.12 are vulnerable; version 1.0.13 (released October 2024) contains the fix — ensure patched version is confirmed before reducing monitoring posture ↗
- ·No known public exploitation has been reported at time of advisory publication, but the vulnerability is pre-authentication RCE with CVSS v3.1 9.8 / CVSS v4 9.3 — treat as critical priority ↗
CVSS provenance
nvdv3.19.8CRITICALCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
nvdv4.09.3CRITICALCVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X
Stop checking back — get the weekly exploitation signal.
Every Monday: what got weaponized or added to CISA KEV in the last seven days — each CVE cross-linked to its PoC, Nuclei template, and detection rule. Free, one email a week, unsubscribe in one click.
CISA ICS
Delta Electronics InfraSuite Device Master
cisa_ics·2024-10-29·CVSS 9.3
[CRITICAL] Delta Electronics InfraSuite Device Master
ICS Advisory
##
Delta Electronics InfraSuite Device Master
Release DateOctober 29, 2024
Alert CodeICSA-24-303-03
Related topics:
Industrial Control System Vulnerabilities, Industrial Control Systems
View CSAF
## 1. EXECUTIVE SUMMARY
- CVSS v4 9.3
- ATTENTION: Exploitable remotely/low attack complexity
- Vendor: Delta Electronics
- Equipment: InfraSuite Device Master
- Vulnerability: Deserialization of Untrusted Data
## 2. RISK EVALUATION
Successful exploitation of this vulnerability could allow an unauthenticated attacker to remotely execute arbitrary code.
## 3. TECHNICAL DETAILS
## 3.1 AFFECTED PRODUCTS
The following versions of InfraSuite Device Master, a real-time device monitoring software, are affected:
- InfraSuite Device Master: Versions 1.0
GHSA
GHSA-r2q9-52vc-q982: Delta Electronics InfraSuite Device Master versions prior to 1
ghsa_unreviewed·2024-10-30
CVE-2024-10456 [CRITICAL] CWE-502 GHSA-r2q9-52vc-q982: Delta Electronics InfraSuite Device Master versions prior to 1
Delta Electronics InfraSuite Device Master versions prior to 1.0.12 are affected by a deserialization vulnerability that targets the Device-Gateway, which could allow deserialization of arbitrary .NET objects prior to authentication.
No detection rules found.
No public exploits indexed.
No writeups or analysis indexed.
2024-10-30
Published