Schneider-Electric Modicon M241 Firmware vulnerabilities
4 known vulnerabilities affecting schneider-electric/modicon_m241_firmware.
Total CVEs
4
CISA KEV
0
Public exploits
1
Exploited in wild
0
Severity breakdown
CRITICAL2HIGH1MEDIUM1
Vulnerabilities
Page 1 of 1
CVE-2021-22699HIGHCVSS 7.5fixed in 5.1.9.12021-05-26
CVE-2021-22699 [HIGH] CWE-20 CVE-2021-22699: Improper Input Validation vulnerability exists in Modicon M241/M251 logic controllers firmware prior
Improper Input Validation vulnerability exists in Modicon M241/M251 logic controllers firmware prior to V5.1.9.1 that could cause denial of service when specific crafted requests are sent to the controller over HTTP.
nvd
CVE-2017-6026CRITICALCVSS 9.1PoC≤ 4.0.3.202017-06-30
CVE-2017-6026 [CRITICAL] CWE-330 CVE-2017-6026: A Use of Insufficiently Random Values issue was discovered in Schneider Electric Modicon PLCs Modico
A Use of Insufficiently Random Values issue was discovered in Schneider Electric Modicon PLCs Modicon M241, firmware versions prior to Version 4.0.5.11, and Modicon M251, firmware versions prior to Version 4.0.5.11. The session numbers generated by the web application are lacking randomization and are shared between several users. This may allow a c
nvd
CVE-2017-6028CRITICALCVSS 9.8≤ 4.0.3.202017-06-30
CVE-2017-6028 [CRITICAL] CWE-522 CVE-2017-6028: An Insufficiently Protected Credentials issue was discovered in Schneider Electric Modicon PLCs Modi
An Insufficiently Protected Credentials issue was discovered in Schneider Electric Modicon PLCs Modicon M241, all firmware versions, and Modicon M251, all firmware versions. Log-in credentials are sent over the network with Base64 encoding leaving them susceptible to sniffing. Sniffed credentials could then be used to log into the web application.
nvd
CVE-2017-6030MEDIUMCVSS 6.5≤ 4.0.3.202017-06-30
CVE-2017-6030 [MEDIUM] CWE-343 CVE-2017-6030: A Predictable Value Range from Previous Values issue was discovered in Schneider Electric Modicon PL
A Predictable Value Range from Previous Values issue was discovered in Schneider Electric Modicon PLCs Modicon M221, firmware versions prior to Version 1.5.0.0, Modicon M241, firmware versions prior to Version 4.0.5.11, and Modicon M251, firmware versions prior to Version 4.0.5.11. The affected products generate insufficiently random TCP initial seque
nvd